Cummins Error Codes

Plain-English meanings for Cummins QuietConnect RS home standby fault codes, taken from Cummins' own operator and service manuals — never from dealer blogs. One warning before you look anything up: Cummins documents two control generations separately, and so do we. The same code number can carry different documented triggers and thresholds on each generation, so every code below lives under its generation. Find your generation first, then your code.

Looking for another brand? Generac error codes and Kohler error codes and Briggs & Stratton error codes and Champion fault indications live in their own hubs — code numbers do not carry over between brands. You can also search all five brands with the Fault Code Lookup tool — choose the Cummins tab and results stay split by generation.

Two generations — find yours first

Operator Panel generation

Operator Panel generation

RS13A, RS14AF, RS20A and RS20AC (models GSBA / GSBB / GSBC) with an in-home Operator Panel. On a fault shutdown the panel's ACTION REQUIRED lamp comes on and the LCD shows the fault description, fault number, and the running hours when the fault occurred; a fault log is viewable on the panel. The control also reports faults as status-light blink codes (explained below). Documented in Cummins operator manual A029V089.

Spec B generation

Spec B generation

RS13A, RS17A, RS20A and RS20AC Spec B (order models C13N6H / C17N6H / C20N6H / C20N6HC) with a local display under the hood. On a fault shutdown the fault lamp comes on and the LCD shows the fault description, fault number, and running hours. Documented in operator manual A062J680 and service manual A062J683, whose §7.12 adds the control's exact trip condition (“Logic”) for many codes.

Sources

Operator Panel generation — blink codes first

On panel-generation units the status indicator light on the control switch inside the generator flashes the fault. First-level codes are single-digit: 1 blink = high engine temperature shutdown; 2 blinks = loss of engine oil pressure; 3 blinks = a service fault (press Stop once to make the two-digit second-level code blink — tens digit, pause, units digit — and Stop again to stop the blinking); 4 blinks = cranking time exceeded 35 seconds. Cummins deliberately never assigned codes 33 and 44, so they cannot be confused with first-level 3 and 4. Blinking stops after five minutes; press Stop three times within three seconds to restore it. The last logged fault blinks even if the condition has been corrected (A029V089 §5.2–§5.4).

1 blink — High Engine Temperature

Operator Panel generation

Shutdown due to high engine temperature (one blink of the status indicator light).

Trigger: One blink indicates shutdown due to high engine temperature (A029V089 §5.2). No threshold or detailed entry is given in this manual.

Explained here — A029V089 gives this code no separate fault entry, so it has no page of its own

3 blinks — Service Fault (pointer to a two-digit code — not a fault by itself)

Operator Panel generation

Three blinks indicate a service fault: a two-digit, second-level shutdown code caused the shutdown. Press Stop once to cause the two-digit code to blink (tens digit, pause, units digit); pressing Stop again stops the blinking. The actual fault number is also shown on the in-home Operator Panel fault screen / fault log.

Trigger: A029V089 §5.2. Cummins deliberately never assigned codes 33 and 44 so they cannot be confused with first-level codes 3 and 4.

Explained here — A029V089 gives this code no separate fault entry, so it has no page of its own

2 blinks and 4 blinks have full entries

The other two first-level codes — 2 blinks (Low Oil Pressure, fault code 2) and 4 blinks (Overcrank, fault code 4) — also appear as numbered faults with full manual entries. They are in the panel-generation table below: Code 2 — Low Oil Pressure Fault and Code 4 — Overcrank.

Operator Panel codes — all 20 verified

Every numbered fault with a full entry in A029V089 §5.4, including codes 78 and 79, which exist only in this generation — they appear in neither Spec B manual. Note that this manual lists causes, not numeric trip thresholds.

CodeFaultTypeWhat it meansManual
2Low Oil Pressure FaultShutdownLoss of engine oil pressure — the engine shut down to protect itself.A029V089
4OvercrankShutdownThe engine cranked through its start attempts without starting/running.A029V089
12OvervoltageShutdownGenerator output voltage too high.A029V089
13UndervoltageShutdownGenerator output voltage too low.A029V089
14OverfrequencyShutdownGenerator output frequency too high.A029V089
15UnderfrequencyShutdownGenerator output frequency too low.A029V089
19Governor Actuator ShutdownShutdownGovernor actuator fault causing shutdown.A029V089
22Governor Actuator OverloadShutdownGovernor actuator overloaded.A029V089
27Voltage Sense LostShutdownThe control lost generator voltage sensing.A029V089
29High Battery VoltageShutdownBattery/charging voltage too high.A029V089
32Low Cranking Speed SenseShutdownCranking speed sensed too low during a start attempt.A029V089
35Control Card FailureShutdownControl card failure.A029V089
36Generator Set Stopped Without Fault ConditionShutdownThe generator set stopped even though no other fault condition was detected — typically a fuel/ignition interruption.A029V089
37Invalid Set ConfigurationShutdownThe generator set configuration stored in the control is invalid.A029V089
43Processor FaultShutdownControl processor fault.A029V089
45Speed Sense FaultShutdownThe control lost engine speed sensing.A029V089
46Generator Set OverloadShutdownThe generator set was overloaded.A029V089
76Alternator Over TempShutdownAlternator over-temperature.A029V089
78Low Fuel PressureShutdownFuel pressure too low.A029V089
79Failure To Transfer To Generator SetFaultThe transfer switch failed to transfer load to the generator set.A029V089

Panel codes in detail

Code 2 — Low Oil Pressure Fault

Shutdown

Loss of engine oil pressure — the engine shut down to protect itself.

A029V089Read the full entry →

Code 4 — Overcrank

Shutdown

The engine cranked through its start attempts without starting/running.

A029V089Read the full entry →

Code 12 — Overvoltage

Shutdown

Generator output voltage too high.

A029V089Read the full entry →

Code 13 — Undervoltage

Shutdown

Generator output voltage too low.

A029V089Read the full entry →

Code 14 — Overfrequency

Shutdown

Generator output frequency too high.

A029V089Read the full entry →

Code 15 — Underfrequency

Shutdown

Generator output frequency too low.

A029V089Read the full entry →

Code 19 — Governor Actuator Shutdown

Shutdown

Governor actuator fault causing shutdown.

A029V089Read the full entry →

Code 22 — Governor Actuator Overload

Shutdown

Governor actuator overloaded.

A029V089Read the full entry →

Code 27 — Voltage Sense Lost

Shutdown

The control lost generator voltage sensing.

A029V089Read the full entry →

Code 29 — High Battery Voltage

Shutdown

Battery/charging voltage too high.

A029V089Read the full entry →

Code 32 — Low Cranking Speed Sense

Shutdown

Cranking speed sensed too low during a start attempt.

A029V089Read the full entry →

Code 35 — Control Card Failure

Shutdown

Control card failure.

A029V089Read the full entry →

Code 36 — Generator Set Stopped Without Fault Condition

Shutdown

The generator set stopped even though no other fault condition was detected — typically a fuel/ignition interruption.

A029V089Read the full entry →

Code 37 — Invalid Set Configuration

Shutdown

The generator set configuration stored in the control is invalid.

A029V089Read the full entry →

Code 43 — Processor Fault

Shutdown

Control processor fault.

A029V089Read the full entry →

Code 45 — Speed Sense Fault

Shutdown

The control lost engine speed sensing.

A029V089Read the full entry →

Code 46 — Generator Set Overload

Shutdown

The generator set was overloaded.

A029V089Read the full entry →

Code 76 — Alternator Over Temp

Shutdown

Alternator over-temperature.

A029V089Read the full entry →

Code 78 — Low Fuel Pressure

Shutdown

Fuel pressure too low.

A029V089Read the full entry →

Code 79 — Failure To Transfer To Generator Set

Fault

The transfer switch failed to transfer load to the generator set.

A029V089Read the full entry →

Spec B codes — all 18 verified

The complete code list from A062J680 §6.4 — exactly 18 codes. Where the A062J683 service manual's “Logic” line was read, the code's page states the exact trip threshold (for example, Code 12 trips above 300 VAC instantly, or above 268 VAC for 3 seconds). For six codes (15, 19, 22, 27, 46, 76) the Logic line was not read, so those pages publish the operator manual's causes only and assert no threshold. There is no code 78, no code 79, and no engine-over-temperature code in this generation.

CodeFaultTypeWhat it meansManual
2Low Oil Pressure FaultShutdownLoss of engine oil pressure — the engine shut down to protect itself.A062J680 / A062J683
4OvercrankShutdownThe engine cranked through its start attempts without starting/running.A062J680 / A062J683
12OvervoltageShutdownGenerator output voltage too high.A062J680 / A062J683
13UndervoltageShutdownGenerator output voltage too low.A062J680 / A062J683
14OverfrequencyShutdownGenerator output frequency too high.A062J680 / A062J683
15UnderfrequencyShutdownGenerator output frequency too low.A062J680
19Governor Actuator ShutdownShutdownGovernor actuator fault causing shutdown.A062J680
22Governor Actuator OverloadShutdownGovernor actuator overloaded.A062J680
27Voltage Sense LostShutdownThe control lost generator voltage sensing.A062J680
29High Battery VoltageShutdownBattery/charging voltage too high.A062J680 / A062J683
32Low Cranking Speed SenseShutdownCranking speed sensed too low during a start attempt.A062J680 / A062J683
35Control Card FailureShutdownControl card failure.A062J680 / A062J683
36Generator Set Stopped Without Fault ConditionShutdownThe generator set stopped even though no other fault condition was detected — typically a fuel/ignition interruption.A062J680 / A062J683
37Invalid Set ConfigurationShutdownThe generator set configuration stored in the control is invalid.A062J680 / A062J683
43Processor FaultShutdownControl processor fault.A062J680 / A062J683
45Speed Sense FaultShutdownThe control lost engine speed sensing while running.A062J680 / A062J683
46Generator Set OverloadShutdownThe generator set was overloaded.A062J680
76Alternator Over TempShutdownAlternator over-temperature.A062J680

Spec B codes in detail

Code 2 — Low Oil Pressure Fault

Shutdown

Loss of engine oil pressure — the engine shut down to protect itself.

A062J680 / A062J683Read the full entry →

Code 4 — Overcrank

Shutdown

The engine cranked through its start attempts without starting/running.

A062J680 / A062J683Read the full entry →

Code 12 — Overvoltage

Shutdown

Generator output voltage too high.

A062J680 / A062J683Read the full entry →

Code 13 — Undervoltage

Shutdown

Generator output voltage too low.

A062J680 / A062J683Read the full entry →

Code 14 — Overfrequency

Shutdown

Generator output frequency too high.

A062J680 / A062J683Read the full entry →

Code 15 — Underfrequency

Shutdown

Generator output frequency too low.

A062J680Read the full entry →

Code 19 — Governor Actuator Shutdown

Shutdown

Governor actuator fault causing shutdown.

A062J680Read the full entry →

Code 22 — Governor Actuator Overload

Shutdown

Governor actuator overloaded.

A062J680Read the full entry →

Code 27 — Voltage Sense Lost

Shutdown

The control lost generator voltage sensing.

A062J680Read the full entry →

Code 29 — High Battery Voltage

Shutdown

Battery/charging voltage too high.

A062J680 / A062J683Read the full entry →

Code 32 — Low Cranking Speed Sense

Shutdown

Cranking speed sensed too low during a start attempt.

A062J680 / A062J683Read the full entry →

Code 35 — Control Card Failure

Shutdown

Control card failure.

A062J680 / A062J683Read the full entry →

Code 36 — Generator Set Stopped Without Fault Condition

Shutdown

The generator set stopped even though no other fault condition was detected — typically a fuel/ignition interruption.

A062J680 / A062J683Read the full entry →

Code 37 — Invalid Set Configuration

Shutdown

The generator set configuration stored in the control is invalid.

A062J680 / A062J683Read the full entry →

Code 43 — Processor Fault

Shutdown

Control processor fault.

A062J680 / A062J683Read the full entry →

Code 45 — Speed Sense Fault

Shutdown

The control lost engine speed sensing while running.

A062J680 / A062J683Read the full entry →

Code 46 — Generator Set Overload

Shutdown

The generator set was overloaded.

A062J680Read the full entry →

Code 76 — Alternator Over Temp

Shutdown

Alternator over-temperature.

A062J680Read the full entry →

Cummins battery & service facts

Battery (Spec B)

Nominal battery voltage 12 VDC; Group 51R; lead acid; minimum 450 CCA (A062J680 §2.5 Specifications, Spec B generation).

Cross-brand trap: Cummins Spec B uses a Group 51R battery — not the Group 26R that Generac Guardian units take. Brand battery specs do not cross-apply.

A062J680 (Issue 2), §2.5 Specifications (p. 23): 'Nominal Battery Voltage 12 VDC; Battery Group 51R; Battery Type Lead Acid; Battery Minimum CCA 450'

Service reminders (Spec B)

Maintenance 'New Event' reminders with yellow service LED: first 25 hours of running, first 100 hours, then every 200 hours of running (A062J680 §5.2).

Generator sets are shipped with 0W-30 synthetic oil (A062J680 §5.1).

Default exercise schedule in the Spec B manual: Tuesday 2:00 pm, monthly, 5 minutes (A062J680 §4.3).

A062J680 (Issue 2), §5.2 (pp. 65–67)

Maintenance tasks (Spec B)

Table 11 (A062J680 §5.2) lists maintenance tasks: check engine oil level; change engine oil and oil filter; adjust valve clearance; replace air filter; clean and check battery (incl. cleaning slip rings); complete system test — against frequency columns: first 25 hours, every 24 hours/6 months, every 100 hours, every 200 hours, every 2 years. The per-task column checkmarks did not survive text extraction cleanly, so the exact task-to-interval mapping is NOT asserted here.

Partially verified — the exact task-to-interval mapping is not asserted

Maintenance kit part numbers

No Cummins maintenance-kit part numbers were verified from a Cummins source this pass. Do not publish kit numbers until checked against a Cummins document. Until then, we publish no Cummins kit numbers at all.

Codes we could not verify

Two code numbers circulate for Cummins home standby units that we could not find in any Cummins manual we read. We flag them here with no meaning attached — publishing a guessed meaning for a fault code is exactly what this site exists not to do.

Code 74 — unverified

unverified — needs manual check Claimed to exist (dealer site). Claimed for RS series by a Cummins dealer page (gshaservices.com), which says Code 74 appears 'only in RS service manuals'

NOT FOUND in any Cummins manual read this pass: A062J680 §6.4 and A062J683 §7.12 list exactly 18 codes (2, 4, 12, 13, 14, 15, 19, 22, 27, 29, 32, 35, 36, 37, 43, 45, 46, 76) and A029V089 §5.4 adds 1, 3, 78, 79 — no 74 anywhere. Full-text search of A062J683 for '74' found no fault code 74. No meaning is asserted.

Code 38 — unverified

unverified — needs manual check Verified for Cummins RV generator sets only — NOT verified for home standby. Cummins RV generator sets (HDKCA/HDKCB) per Cummins manual A043D713; a dealer page claims a home-standby Code 38 exists only on the GSAA 12 kW

Cummins' RV manual A043D713 (HDKCA/HDKCB) does list Code 38 = 'Over Current (Field Overload)' — but that is an RV generator set manual, a different product line. Code 38 does NOT appear in any home standby manual read (A029V089, A062J680, A062J683). The GSAA-only claim could not be verified because no GSAA manual was read. Do NOT publish the RV meaning as a home standby meaning.

41 / 42 / 48 / 57 (and other RV-only codes): A043D713 lists additional codes beyond the home standby set (e.g., 41, 42, 48, 57) for RV sets that share this control-code family. They were NOT read into this dataset and must not be presented as RS home standby codes.

3-digit PowerCommand-style codes (e.g., 'Fault Code 143', 'Fault Code 359' attributed to the RS20A by third-party articles): The RS home standby manuals' own code list is the two-digit set in this file. Three-digit codes belong to Cummins PowerCommand commercial controls (and SPN/FMI codes to yet another system). Articles assigning 143/359-style codes to an RS20A conflict with Cummins' own RS manuals and were not used.

Coverage gaps

Safety note: StandbyWise publishes lookup information only — no gas-line, transfer-switch wiring, or internal repair instructions. Most Cummins RS codes are dealer-level by Cummins' own instruction; the code pages gate those to a Cummins service representative or authorized dealer. See our disclaimer.