Champion hub
Champion Generator Fault Indications
Champion standby generators don't use error codes
If you came here searching for a Champion “error code”, this is the honest answer first: no Champion home standby manual — in any of the three controller generations — displays, lists, or references a numbered or lettered fault code. Faults are named indications: a labeled LED lights on the earlier Engine Control Module, and a named icon lights on the aXis and fleX controller displays. Champion's manuals do use the phrase “fault code” generically (section titles like “Fault Code Reset”, a pre-start checklist item “No fault code LEDs are lit”), but the “code” is always a named LED or icon — never a number. Every generation also lights a red exterior warning LED on the back of the enclosure (Champion's own part name for it in early manuals: “Exterior Fault Code Indicator Light”) — check it weekly; if it is on, open the enclosure and read which LED or icon is lit.
Looking for another brand? Generac error codes, Kohler error codes, Cummins error codes and Briggs & Stratton error codes live in their own hubs. You can also search all five brands with the Fault Code Lookup tool — choose the Champion tab and results stay split by generation.
Three generations — find yours first
Labeled LEDs, no display
Generation 1 — ECM (labeled LEDs)How to tell: your unit (e.g. model 100136, 12.5 kW) has an Engine Control Module with labeled LEDs and an ATS/OFF/Manual switch — no screen, no icons.
Model 100136 family (12.5 kW) per Operator's Manual REV 20231107, pp. 15–17
Named RED icons + LCD
Generation 2 — aXis Controller (fault icons)How to tell: an aXis Controller touch pad (MAN / AUTO / OFF / MODE) with an LCD that cycles DCV / HZ / ACV / HR readings. Faults light as named RED icons.
All aXis Controller models; text verified in Operator's Manual 100515 (14 kW) pp. 17–19 and aXis Installation Manual pp. 30–33 (identical fault-icon text in both)
Named icons on an OLED display
Generation 3 — fleX Controller (OLED fault icons)How to tell: a fleX Controller with an OLED display and Wi-Fi ATS settings pages (models 201391–201244, 10–26 kW). Faults light as named icons, and Over Crank flashes with a lockout countdown.
Models 201391 (10 kW), 201249 (18 kW), 201202 (22 kW), 201244 (26 kW); text verified in Operator's Manual 201391 (5900-M-OP REV 20261111) pp. 24–28
Sources
- Operator's Manual, Model #100136 — 12.5-kW Home Standby Generator (REV 20231107) — Champion Power Equipment (Champion PDF reproduced by Northern Tool)
- Operator's Manual, Model #100515 — 14-kW Home Standby Generator (REV 20210207) — Champion Global Power Equipment (Champion manual reproduced by ManualsLib)
- aXis Controller Home Standby Generator Installation Manual — Champion Power Equipment (Champion manual reproduced by ManualsLib)
- Operator's Manual, Model #201391 — 10-kW Home Standby Generator with fleX Controller (5900-M-OP, REV 20261111) — Champion Power Equipment
Generation 1 — ECM labeled LEDs (5 fault LEDs)
A named LED lights on the Engine Control Module; the separate Exterior Fault Code Indicator Light on the back of the enclosure also lights (manual: check it weekly). If the exterior light is on, open the enclosure, read which module LED is lit, remedy or call an authorized Service Dealer / Champion Customer Service 1-877-338-0999. The module also has green Exercise, Run and Power status LEDs, which are not faults.
Low Battery LED
Warning — no shutdownShows as: YELLOW LED lit on Engine Control Module
Battery voltage fell below 21.0 volts for at least one minute while the engine was running. LED turns off if battery voltage rises above 21.1 volts. Battery voltage is NOT monitored while cranking.
Read the ECM (labeled LEDs) entry →High Engine Temp LED
ShutdownShows as: RED LED lit on module AND on enclosure exterior
Engine operating temperature exceeds factory preset limits.
Read the ECM (labeled LEDs) entry →Hz Over / Under Speed LED
ShutdownShows as: RED LED lit
Engine operating above or below its preset speed limit.
Read the ECM (labeled LEDs) entry →Low Oil LED
ShutdownShows as: RED LED lit
Engine oil level dropped below the safe operating level.
Read the ECM (labeled LEDs) entry →Over Crank LED
ShutdownShows as: RED LED lit
Engine tried to start but could not start in the specified time; the engine tries to start five times before the light turns on. Manual notes this may occur on initial start-up while the fuel system pressurizes.
Read the ECM (labeled LEDs) entry →Generation 2 — aXis Controller fault icons (8 icons)
The specific fault icon lights RED on the aXis Controller module and the exterior LED lights. Per 'Fault protection': in all cases a RED icon means the HSB has registered a fault that must be corrected. ONLY the LOW BATTERY and MAINTENANCE icons do not latch out or shut down the HSB; ALL other RED icon faults latch out, shut down, disable starting, and light the controller icon + exterior fault icon. Crank cycle on this generation: Approximate starter crank cycle: 10 seconds ON / 10 seconds OFF, 5 cycles total; failure to start lights the OVER CRANK icon.
Low Oil
ShutdownShows as: RED icon (controller + exterior LED)
Engine oil LEVEL drops below the safe operating level. (Note: aXis text says oil level; the fleX manual words its equivalent as oil PRESSURE — see conflicts.)
Read the aXis Controller (fault icons) entry →High Engine Temperature
ShutdownShows as: RED icon (controller + exterior LED)
Engine operating temperature exceeds factory preset limits; manual notes possible causes: excessive load or high ambient temperatures.
Read the aXis Controller (fault icons) entry →Over Crank
ShutdownShows as: RED icon (controller + exterior LED)
Engine does not start after 5 attempts (crank cycle 10 s ON / 10 s OFF × 5).
Read the aXis Controller (fault icons) entry →Hz Over Speed / Under Speed
ShutdownShows as: RED icon (controller + exterior fault LED)
Engine operating above or below its preset (factory-set) speed limits.
Read the aXis Controller (fault icons) entry →Line Over Voltage
ShutdownShows as: RED icon (controller + exterior fault LED)
Generator output exceeds preset limit of 257 VAC.
Read the aXis Controller (fault icons) entry →Line Under Voltage
ShutdownShows as: RED icon (controller + exterior fault LED)
Generator output below preset limit of 190 VAC.
Read the aXis Controller (fault icons) entry →Low Battery
Warning — no shutdownShows as: RED icon
Battery voltage falls below 21.0 volts for at least 5 seconds WHILE THE ENGINE IS RUNNING. Icon turns off if battery voltage rises above 22 volts. Battery voltage is NOT monitored during cranking.
Read the aXis Controller (fault icons) entry →Requires Maintenance
Warning — no shutdownShows as: RED icon
The HSB generator is ready for maintenance (maintenance reminder hours, programmable on the controller — 'Hours for maintenance reminder' setting in Programming aXis Controller).
Read the aXis Controller (fault icons) entry →Generation 3 — fleX Controller fault icons (9 icons)
The specific fault icon lights on the fleX Controller and the warning LED on the controller and exterior lights. Per 'Fault Protection' (p. 28): only the LOW BATTERY and MAINTENANCE icons do not latch out or shut down the HSB; ALL other icon faults latch out, shut down, disable starting, and light the icon + exterior warning LED. Note that fleX splits speed faults into two separate icons (Hz Over Speed and Under Speed) where the earlier generations combine them, and names its oil fault “Low Oil Pressure Shutdown” where the earlier manuals say oil level — each page keeps its own generation's wording.
Low Oil Pressure Shutdown
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Engine oil PRESSURE drops below a safe operating level. (fleX wording is pressure; aXis/ECM wording is oil level — preserved as a wording difference, not merged.)
Read the fleX Controller (OLED fault icons) entry →High Engine Temperature
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Engine operating temperature exceeds factory preset limits; possible causes per manual: excessive load or high ambient temperatures.
Read the fleX Controller (OLED fault icons) entry →Over Crank
ShutdownShows as: OVER CRANK icon FLASHES on the fleX Controller; exterior warning LED steady lit
HSB does not start within the mode-dependent crank cycles (see crank_cycle_by_mode).
Read the fleX Controller (OLED fault icons) entry →Hz Over Speed
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Engine operating above its preset speed limits (factory set). Listed as a separate mode entry from Under Speed in the fleX manual (the descriptive text covers above/below together).
Read the fleX Controller (OLED fault icons) entry →Under Speed
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Engine operating below its preset speed limits (factory set). Separate mode entry in the fleX manual.
Read the fleX Controller (OLED fault icons) entry →Line Over Voltage
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Generator output exceeds preset limits of 258–290 VAC lasting 0.5 seconds, or greater than 290 VAC lasting 0.03 seconds; condition evaluated after running 6 seconds. (DIFFERS from aXis single 257 VAC threshold — see conflicts.)
Read the fleX Controller (OLED fault icons) entry →Line Under Voltage
ShutdownShows as: Icon lit; warning LED on controller and exterior lit
Generator output below preset limit of 216 VAC lasting 0.5 seconds; condition evaluated after running 10 seconds. (DIFFERS sharply from aXis 190 VAC — see conflicts.)
Read the fleX Controller (OLED fault icons) entry →Low Battery
Warning — no shutdownShows as: Icon lit; warning LED on controller and exterior lit
Battery voltage falls below 21.0 volts for at least 2 seconds while the engine is running (aXis: 5 seconds; ECM LED: 1 minute and 21.1 V clear — see conflicts). Icon turns off if voltage rises above 22 volts. NOT monitored during cranking.
Read the fleX Controller (OLED fault icons) entry →Maintenance
Warning — no shutdownShows as: Icon lit
HSB requires maintenance. The NEXT SERVICE meter counts down from 100 hours to 0; reset when it reaches 0 (see 'Resetting the Maintenance Hour Meter').
Read the fleX Controller (OLED fault icons) entry →Resetting a fault
Generation 1 — ECM (labeled LEDs)
Place the Engine Control Module switch in the OFF position — this resets the fault LED. If the fault recurs it must be addressed (manual section 'Reset Fault Code(s)', p. 16/17).
Generation 2 — aXis Controller (fault icons)
'Fault Code Reset': push OFF button to reset, then MAN or AUTO button to re-arm. Correct the fault before resetting.
Generation 3 — fleX Controller (OLED fault icons)
'Fault Code Reset' (p. 28): 1) fault has occurred, 2) push OFF button to reset, 3) then AUTO or MAN to re-arm. Correct faults before resetting. For Over Crank specifically, the 120-second starter lockout timer must count down to zero before another start attempt, regardless of when OFF is pressed; remaining lockout shows on the display below the lock icon.
In short, on the icon generations: OFF button first, then MAN/AUTO — and always correct the fault before resetting, or it will simply come back.
Battery — a 24 V system, not 12 V
24 V DC starting/control system on ALL generations read (aXis Installation Manual: 'Power ON (24VDC)'; Champion product pages: '24V starting system', operates to -22 °F). This is a major differentiator from Generac/Kohler/Briggs 12 V systems — do not present Champion batteries as 12 V system parts. Two (2) 12 volt Group U1 batteries wired in SERIES (positive of one to negative of the other via series cable) for 24 V. Batteries NOT included; purchase locally. Install positive cable first; always connect the positive battery cable to the generator first. Size: 7 3/4 L x 5 3/16 W x 7 5/16 H inches (196 x 131 x 185 mm), post style.
Cold-cranking amps — as each manual states it
- aXis manual (100515): Minimum 350 CCA EACH (Operator's Manual 100515, p. 22: 'Two (2) 12 volt Group U1 batteries with a minimum of 350 CCA each')
- ECM (100136) and fleX (201391) manuals: Recommended battery type for typical use is 350 CCA (based on testing -22 °F/-30 °C to 104 °F/40 °C); a 300 CCA battery from the Recommended Battery Type chart may be used in regularly warmer climates (100136 p. 20; 201391 p. 39)
- Group name variant, preserved: 100515 manual says 'Group U1'; 100136 and 201391 manuals say 'Group U1L'. Preserved as printed.
100515 Operator's Manual p. 22; 100136 Operator's Manual p. 20; 201391 Operator's Manual p. 39; battery maintenance: 100515 p. 26
Charger 100482 and the NO CHARGE indication
Champion automatic battery charger, Champion model 100482 (label in manuals), output 24 Vdc 1.6 A, input 80–125 Vac 1.0 A 50/60 Hz, UL Std. 1236; for lead-acid (LA/SLA), AGM, or Gel batteries — NOT lithium-ion (charger label, 100136 manual p. 17/18). Charger senses state of charge and charges automatically; LEDs on the charger display charge state.
- Power: Lit to indicate the battery is fully charged (pairing as printed in the manual's charger label artwork, 100136 p. 18 / 100515 p. 20)
- Small Bar: Lit to indicate the battery is receiving a trickle charge
- Middle Bar: Lit to indicate current output is near 50%
- Large Bar: Lit to indicate the charger is operating above 50% capacity
- No Charge: Lit to indicate a battery charging problem. If this LED is lit, the LOW BATTERY LED/icon on the engine/aXis/fleX controller will also be lit.
The fleX manual's Battery Charger section (201391, p. 36) describes the charger LEDs differently in the portion read — including 'Low Trickle Charge: when no yellow LEDs are lit, the charger is in low trickle charge state.' The full fleX charger LED table was not captured in this pass; recorded as partially verified — see gaps.
Owner battery maintenance in Champion's manuals: inspect battery cables and terminals for corrosion; check cables are securely fastened; check ground lug connections are tight; check fluid level unless sealed; top off with distilled water only; inspect and clean battery terminals (monthly, per maintenance chart).
Exercise behavior, by generation
ECM — switch with built-in timer
Once every 7 days (168 hours) the engine starts and runs 15 minutes; load transfer does not occur unless utility power is lost. Set by pressing the exercise switch ON at the desired day/time; the time must be reset after a battery disconnect or if the switch was moved to OFF. The Exercise LED flashes green during the cycle and stays lit when it completes.
aXis — programmable schedule
Programmed on the aXis Controller: 0 = no exercise, 1 = once per month, 2 = twice per month, 3 = four times per month, 4 = weekly, with day, hour and minute settable. BLUE icons are lit during the exercise period. Exercise duration is not stated in the aXis manual text read — do not assume the 15 minutes verified for the other generations applies here.
fleX — 15 minutes, with an internal conflict
Programmable via fleX user settings or the ATS Wi-Fi page (frequency default None; day and start time settable; controller must be in AUTO). Duration is system-set at 15 minutes per the Wi-Fi section (“The duration is not adjustable”) — but the same manual's user-settings table lists “Exercise Time: exercise duration from 1–100 minutes, default 15min”. Both statements are in the 201391 manual (REV 20261111); the conflict is Champion's, and we record it unresolved rather than pick one.
Maintenance summaries, by generation
ECM & aXis charts (100136 / 100515)
- First 5 hours: change engine oil (100136 adds the filter; it also requires oil and filter changes every 100 hours).
- Weekly: check the exterior fault/warning LED; inspect and clean enclosure louvers.
- Monthly: check engine oil level (or every 24 hours of continuous operation), inspect fuel lines and connections, inspect and clean battery terminals.
- Every 2 years or 100 hours: change engine oil, inspect/clean air cleaner, inspect spark plug, reset the maintenance hour meter every 100 hours (100136), and a complete inspection / tune-up / valve-lash check by a service dealer.
- Oil: API Service Class SN or better; 5W-30 full synthetic recommended. Spark plug gap is model-specific: 0.022–0.028 in. (100136; OEM F7RTC) vs 0.028–0.031 in. (100515).
fleX chart (201391)
- First 25 hours: change engine oil; oil changes are required every 100 hours.
- Weekly: check the exterior warning LED; inspect and clean enclosure louvers.
- Monthly: check engine oil level (or every 24 hours of continuous operation), inspect fuel lines and connections, inspect and clean battery terminals.
- Every 2 years or 100 hours: change engine oil when the maintenance light comes on, inspect/clean air cleaner, inspect spark plug, reset the maintenance hour meter every 100 hours, and a complete inspection / tune-up / valve-lash check by a service dealer.
- Oil: API SN or better; 0W-40 full synthetic recommended for the 10 kW fleX (differs from the earlier manuals' 5W-30 — model-specific). Spark plug OEM Champion RC12YC, gap 0.024–0.031 in.
One more honest gap: no Champion standby maintenance-kit part number exists in any manual read — Champion sells parts individually via its parts lists, so unlike the Generac kit pages elsewhere on this site, there is no Champion kit number to publish, and we do not invent one.
What we could not verify
- E0–E20 (and similar) 'error code' lists for Champion standby generators: NOT FOUND in any Champion manufacturer source; third-party only; treated as fabricated (see headline_finding.e_code_trap). No E-code entries exist in this dataset.
- Current-production aXis models with the 4-inch color display (e.g. 100838, 14 kW): manual not read in this pass — whether the fault icon set/thresholds match the 100515 icon-pad aXis text is UNVERIFIED.
- Model 100177 (8.5 kW select-circuit) and model 100294 (14 kW, 2018-era): manuals not read in this pass; controller generation and fault indications UNVERIFIED. Do not assume ECM text covers them beyond the 100136 family actually read.
- aXis exercise duration (minutes per exercise run): not stated in the aXis/100515 text read — UNVERIFIED.
- ECM generation: a maintenance light is referenced by the 100136 maintenance chart but no labeled maintenance LED is described in the ECM section read — indication details UNVERIFIED.
- fleX battery charger LED table: only partially captured (low trickle charge = no yellow LEDs lit, 201391 p. 36); full fleX charger LED meanings UNVERIFIED in this pass. The 5-LED charger label meanings recorded are from the ECM/aXis manuals.
- fleX manuals for 18/22/26 kW (201249/201202/201244): model list verified from the fleX Installation Manual; fault text was verified in the 201391 (10 kW) operator's manual and spot-confirmed in the 201244 (26 kW) manual (same fault icon structure, AVR wording) — full per-model threshold re-verification not done.
- No Champion standby maintenance KIT part numbers were found in the manuals read (Champion sells parts individually via its parts lists; no Generac-style scheduled-maintenance kit number is stated) — do not invent kit numbers.
- 100515 spark plug TYPE (only the gap/torque were captured) and 100515 oil filter part number: not captured in this pass — UNVERIFIED here (100136 and 201391 values are recorded per model and must not be copied across).
Safety note: StandbyWise publishes lookup information only — no gas-line, transfer-switch wiring, or internal repair instructions. Most Champion fault remedies in Champion's own manuals end at “contact Champion or your nearest Authorized Champion Dealer”, and the indication pages gate those accordingly — AVR adjustment and manometer fuel-pressure checks are dealer/installer work, never owner steps here. See our disclaimer.