Kohler Error Codes
Plain-English meanings for Kohler standby generator fault messages, taken from Kohler's own operation manuals — never from dealer blogs. Unlike Generac, Kohler publishes no web fault-code hub: its fault documentation is manual-only, so every message below is cited to the specific Kohler manual (TP number and section) it came from. This page covers the current RDC2 controller in full, plus the older ADC 2100 / DC 2200 two-letter codes in a separate section — the two systems name the same faults differently, so we never merge them.
Looking for Generac instead? The Generac error-code hub covers Generac codes — Generac codes live there, Kohler codes live here. You can also search the verified database with the Fault Code Lookup tool.
Warnings vs shutdowns — how the RDC2 controller behaves
Warning (W)
On RDC2, a warning displays a fault message but the set does not shut down; the controller resets automatically after the warning condition is corrected (TP-7092 §2.5.1).
Shutdown (SD)
On RDC2, a shutdown stops the set automatically and displays a fault message; the OFF LED flashes; on some faults the engine cooldown cycle runs before shutdown (marked * in the tables). Shutdown switches reset when the problem is corrected, but the controller fault does not clear until the controller is reset; the set cannot be restarted until the fault is corrected and the controller is reset (TP-7092 §2.5.2, §2.5.5).
Kohler's own reset rule, stated as the manuals state it: always identify and correct the cause before resetting — the set cannot be restarted until the fault is corrected and the controller is reset. In the tables below, a shutdown marked “cooldown first” runs the engine cooldown cycle before stopping on some faults.
Sources
- TP-7092 2/21 (also 9/23 rev.), Operation — 14RCA/14RCAL, 20RCA/20RCAL class residential standby, Controller: RDC2 — Kohler Co. official manual, as reproduced on ManualsShelf/ManualsFile (Kohler does not surface this PDF in search on resources.kohler.com) (§2.5 Faults and Figure 2-5 Controller Fault Messages (p. 31))
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
RDC2 fault messages — all 26 verified
Current controllers on the RCA and RESV lines. Click a message to jump to its full entry — meaning, trigger, and the checks Kohler's table itself lists.
| Displayed message | Type | What it means | Manual |
|---|---|---|---|
| AC Sens Loss | ShutdownWarning (1 sec) / Shutdown (3 sec) | AC sensing lost — in Auto mode, generator output AC sensing is lost. | TP-6880 (RESV) |
| Accy PwrOver Warning | WarningWarning | Accessory Power Overload — an over-current fault (short circuit) on the accessory controller power output. | TP-6880 (RESV) |
| Advanced Diagnostic | ShutdownShutdown (event history only) | Shutdown during the reduced-speed portion of an exercise. | TP-6880 (RESV) |
| Alt Protect | ShutdownShutdown | High generator current detected; the set shuts down to protect the alternator from damage caused by overheating the windings. | TP-6880 (RESV) |
| ATS ComError | WarningWarning | ATS communication error — warning is displayed if the ATS (Model RXT) interface connection is lost. | TP-6880 (RESV) |
| ATS PhaseRot | WarningWarning | ATS phase rotation mismatch — transfer switch phase rotation does not match; the ATS will not transfer. | TP-6880 (RESV) |
| Aux Input | ShutdownShutdown (cooldown first) | Auxiliary input — an optional customer-connected input is closed (digital input from optional PIM). | TP-6880 (RESV) |
| Batt Chg Flt | WarningWarning | Battery charger fault — input to the PIM from an external battery charger (NOT the built-in battery charger). | TP-6880 (RESV) |
| Battery High | WarningWarning | Engine starting battery voltage high. | TP-6880 (RESV) |
| Battery Low | WarningWarning | Engine starting battery voltage low. | TP-6880 (RESV) |
| Battery CrLo Warning | WarningWarning | Critically low engine starting battery voltage. | TP-6880 (RESV) |
| Eng Speed High | ShutdownShutdown (cooldown first) | Engine overspeed — Kohler's overspeed equivalent on RDC2 (there is no message literally named 'Overspeed' in the RDC2 table). | TP-6880 (RESV) |
| Eng Speed Low | ShutdownShutdown (cooldown first) | Engine underspeed. | TP-6880 (RESV) |
| Exer Not Sch | WarningWarning | Exercise not scheduled — no exercise is scheduled on the controller. | TP-6880 (RESV) |
| Frequency High | ShutdownShutdown (cooldown first) | Governed frequency high (overfrequency). | TP-6880 (RESV) |
| Frequency Low | ShutdownShutdown (cooldown first) | Governed frequency low (underfrequency). | TP-6880 (RESV) |
| Lo Crank Vlt | WarningWarning | Low cranking voltage. | TP-6880 (RESV) |
| Locked Rotor | ShutdownShutdown | No engine rotation is sensed during cranking (Kohler's locked-rotor / no-rotation start failure). | TP-7092 (RCA) |
| MainPwrOverL | ShutdownShutdown | Main power overload — an over-current fault on the 70 controller power output (short circuit). | TP-6880 (RESV) |
| Not in Auto | WarningWarning | The generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored. | TP-6880 (RESV) |
| Oil Press Low | ShutdownShutdown (cooldown first) | Low oil pressure shutdown (LOP switch). Kohler notes the low oil pressure shutdown does not protect against low oil level. | TP-6880 (RESV) |
| Over Crank | ShutdownShutdown | Overcrank — the generator failed to start. | TP-6880 (RESV) |
| Spd Sens Flt | ShutdownShutdown | Engine speed sensor fault — the speed sensor has failed or the engine stalled. This is Kohler's RPM/speed-signal-loss equivalent on RDC2. | TP-6880 (RESV) |
| Total Power High | ShutdownShutdown | Measured load exceeds the generator set rating. | TP-6880 (RESV) |
| Volts L1-L2 High | ShutdownShutdown (cooldown first) | Generator output voltage high (overvoltage). | TP-6880 (RESV) |
| Volts L1-L2 Low | ShutdownShutdown (cooldown first) | Generator output voltage low (undervoltage). | TP-6880 (RESV) |
RDC2 messages in detail
AC Sens Loss
ShutdownVerified against a Kohler manual- What this message means
- AC sensing lost — in Auto mode, generator output AC sensing is lost.
- What triggers it
- Detection begins 10 seconds after crank disconnect. Warning after 1 second if no output detected after crank disconnect; shutdown after 3 seconds if voltage was present and then lost.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Accy PwrOver Warning
WarningVerified against a Kohler manual- What this message means
- Accessory Power Overload — an over-current fault (short circuit) on the accessory controller power output.
- What triggers it
- Over-current on the accessory controller power output.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Advanced Diagnostic
ShutdownVerified against a Kohler manual- What this message means
- Shutdown during the reduced-speed portion of an exercise.
- What triggers it
- Fault during reduced-speed exercise; event history shows 'Advanced Diagnostic Active'; the engine then restarts, runs at full speed for 2 minutes, and stops; controller returns to AUTO and the exercise schedule does not change.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- If the generator set does not restart and return to AUTO, check for other faults (per source).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Alt Protect
ShutdownVerified against a Kohler manual- What this message means
- High generator current detected; the set shuts down to protect the alternator from damage caused by overheating the windings.
- What triggers it
- High generator current (10RESV and 12RESV only).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Reduce the load.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
ATS ComError
WarningVerified against a Kohler manual- What this message means
- ATS communication error — warning is displayed if the ATS (Model RXT) interface connection is lost.
- What triggers it
- Loss of connection to the transfer switch interface board (§2.5.3).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check communication wiring between transfer switch interface board and generator set.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
ATS PhaseRot
WarningVerified against a Kohler manual- What this message means
- ATS phase rotation mismatch — transfer switch phase rotation does not match; the ATS will not transfer.
- What triggers it
- Phase rotation mismatch at the transfer switch.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Correct the ATS connection — dealer-level (source refers to ATS installation manual/wiring diagrams).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Aux Input
ShutdownVerified against a Kohler manual- What this message means
- Auxiliary input — an optional customer-connected input is closed (digital input from optional PIM).
- What triggers it
- Optional PIM digital input closed.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check customer-supplied equipment.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Batt Chg Flt
WarningVerified against a Kohler manual- What this message means
- Battery charger fault — input to the PIM from an external battery charger (NOT the built-in battery charger).
- What triggers it
- Signal from an external battery charger via the PIM.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check the external battery charger.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Battery High
WarningVerified against a Kohler manual- What this message means
- Engine starting battery voltage high.
- What triggers it
- Battery voltage rises above 16 VDC for more than 10 seconds; inhibited during the engine crank cycle; clears when voltage returns to an acceptable level.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check the battery rating and condition.
- Check the battery charger operation.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Battery Low
WarningVerified against a Kohler manual- What this message means
- Engine starting battery voltage low.
- What triggers it
- Battery voltage falls below 12.5 VDC for more than 90 seconds when the engine is not running; not operative during the crank cycle; clears when voltage returns to an acceptable level.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check the battery rating and condition.
- Check the battery charger operation.
- Charge or replace the battery.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Battery CrLo Warning
WarningVerified against a Kohler manual- What this message means
- Critically low engine starting battery voltage.
- What triggers it
- Battery voltage falls below 11 V for more than 10 seconds; inhibited during the crank cycle; clears when voltage returns to an acceptable level.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check the battery rating and condition.
- Check the battery charger operation.
- Charge or replace the battery.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Eng Speed High
ShutdownVerified against a Kohler manual- What this message means
- Engine overspeed — Kohler's overspeed equivalent on RDC2 (there is no message literally named 'Overspeed' in the RDC2 table).
- What triggers it
- Engine speed exceeds 115% of normal running speed for more than 0.3 seconds.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Eng Speed Low
ShutdownVerified against a Kohler manual- What this message means
- Engine underspeed.
- What triggers it
- Engine speed drops below 85% of normal running speed for more than 3 seconds.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Reduce the load.
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Exer Not Sch
WarningVerified against a Kohler manual- What this message means
- Exercise not scheduled — no exercise is scheduled on the controller.
- What triggers it
- No exercise schedule set.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- See §3.6 of the manual for setting the exerciser (owner-level controller setting).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Frequency High
ShutdownVerified against a Kohler manual- What this message means
- Governed frequency high (overfrequency).
- What triggers it
- Frequency exceeds 110% of the system frequency setpoint for more than 10 seconds; function becomes active 10 seconds after engine start (10-second inhibit).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Frequency Low
ShutdownVerified against a Kohler manual- What this message means
- Governed frequency low (underfrequency).
- What triggers it
- Frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the setting for more than 60 seconds; 10-second inhibit after start.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Reduce the load and restart the generator set.
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Lo Crank Vlt
WarningVerified against a Kohler manual- What this message means
- Low cranking voltage.
- What triggers it
- TP-6880: battery voltage falls below 8 VDC for more than 6 seconds while the starter is engaged. TP-7092 (14/20RCA) states it differently: battery voltage dropped below 3.5 VDC during engine cranking (no duration stated).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Charge or replace the battery.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Locked Rotor
ShutdownVerified against a Kohler manual- What this message means
- No engine rotation is sensed during cranking (Kohler's locked-rotor / no-rotation start failure).
- What triggers it
- Shuts down 3 seconds after the fault is detected.
- Applies to
- RDC2 — 14RCA/14RCAL, 20RCA/20RCAL class (TP-7092); not present in the TP-6880 RESV table read
- Checks Kohler lists
- Check the battery.
- Check for loose connections.
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-7092 2/21 (also 9/23 rev.), Operation — 14RCA/14RCAL, 20RCA/20RCAL class residential standby, Controller: RDC2 — Kohler Co. official manual, as reproduced on ManualsShelf/ManualsFile (Kohler does not surface this PDF in search on resources.kohler.com) (§2.5 Faults and Figure 2-5 Controller Fault Messages (p. 31))
MainPwrOverL
ShutdownVerified against a Kohler manual- What this message means
- Main power overload — an over-current fault on the 70 controller power output (short circuit).
- What triggers it
- Over-current/short circuit on the controller's main power output.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
- Manual's check column also lists checking for a shorted run relay and wiring for short circuits — dealer-level, not transcribed as steps.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Not in Auto
WarningVerified against a Kohler manual- What this message means
- The generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.
- What triggers it
- Controller not in AUTO.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Press AUTO to place the generator set in Automatic mode, when appropriate.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Oil Press Low
ShutdownVerified against a Kohler manual- What this message means
- Low oil pressure shutdown (LOP switch). Kohler notes the low oil pressure shutdown does not protect against low oil level.
- What triggers it
- The LOP switch indicates low oil pressure for more than 5 seconds; function becomes active 30 seconds after crank disconnect (30-second inhibit).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check for leaks in the lubrication system.
- Check the oil level and add oil if the level is low.
- Check the oil pressure switch and wiring — dealer-level beyond the oil-level check.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Over Crank
ShutdownVerified against a Kohler manual- What this message means
- Overcrank — the generator failed to start.
- What triggers it
- Three unsuccessful starting attempts.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Check the fuel supply, spark plug, and battery.
- Check for loose connections.
- Contact an authorized distributor/dealer for service if the problem continues (dealer-level beyond the listed checks).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Spd Sens Flt
ShutdownVerified against a Kohler manual- What this message means
- Engine speed sensor fault — the speed sensor has failed or the engine stalled. This is Kohler's RPM/speed-signal-loss equivalent on RDC2.
- What triggers it
- Speed sensor failure or engine stall.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Total Power High
ShutdownVerified against a Kohler manual- What this message means
- Measured load exceeds the generator set rating.
- What triggers it
- Load greater than 102% of the generator set power rating for more than 1 minute (10RESV and 12RESV only).
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Reduce the load.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Volts L1-L2 High
ShutdownVerified against a Kohler manual- What this message means
- Generator output voltage high (overvoltage).
- What triggers it
- Output voltage exceeds 120% of system nominal voltage for more than 2 seconds.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Volts L1-L2 Low
ShutdownVerified against a Kohler manual- What this message means
- Generator output voltage low (undervoltage).
- What triggers it
- Output voltage falls below 80% of nominal system voltage for more than 10 seconds.
- Applies to
- RDC2 — 8/10/12RESV(L) (TP-6880)
- Checks Kohler lists
- Reduce the load and restart the generator set.
- Model 20RCA/20RCAL only (TP-7092): check the enclosure thermostat and reset if tripped — see manual §5.6.
- Contact an authorized distributor/dealer for service (dealer-level).
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)
Legacy codes — ADC 2100 / DC 2200 (12RES era)
Separate system, separate names. Older Kohler controllers (ADC 2100 and DC 2200, 12RES era) show short two-letter codes instead of RDC2 message text — overspeed is literally “OS” here, where RDC2 says “Eng Speed High.” This section is kept separate on purpose; do not read an RDC2 meaning into a legacy code or the other way around.
| Code | Message | Type | Meaning & trigger (per Kohler) | Checks Kohler lists |
|---|---|---|---|---|
| AF | Auxiliary Fault | Shutdown (input shutdown) | Auxiliary fault, input shutdown — listed as 'Not used' on the 12RES. Trigger: Auxiliary input shutdown (not used on this model). |
|
| HE | High Engine Temperature | Shutdown | High engine temperature shutdown. Trigger: Engine coolant temperature exceeds the maximum temperature for more than 5 seconds; protective becomes active after the engine reaches crank disconnect speed. |
|
| LB | Low Battery Voltage | Warning (does not shut down) | Low engine starting battery voltage warning. Trigger: DC 2200 table (TP-6398): battery voltage falls below 8 VDC (12 VDC system) or 16 VDC (24 VDC system) for more than 10 seconds when the engine is not running. |
|
| LCL / LOC | Low Coolant Level / Loss of Coolant | Shutdown (listed) | Low coolant level / loss of coolant — both listed as not used on air-cooled models. Trigger: Not used on air-cooled 12RES. |
|
| LOP | Low Oil Pressure | Shutdown | Low oil pressure shutdown. The manual notes this shutdown does not protect against low oil level. Trigger: Low oil pressure condition exists for more than 5 seconds; protective becomes active 30 seconds after the engine has reached crank disconnect speed (30-second inhibit). |
|
| OC | Overcrank | Shutdown | Overcrank shutdown — the generator failed to start. Trigger: After 3 unsuccessful starting attempts; the crank cycle is three attempts of 15 seconds cranking and 15 seconds rest. The set also shuts down if no engine rotation is sensed during cranking (1 second after detection). |
|
| OF | Overfrequency | Shutdown | Overfrequency shutdown. Trigger: Governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds. |
|
| OS | Overspeed | Shutdown | Overspeed shutdown (on these older controllers the message is literally 'Overspeed', unlike RDC2's 'Eng Speed High'). Trigger: Engine speed exceeds 115% of normal running speed for more than 0.3 seconds. |
|
| OU | Overvoltage | Shutdown | Overvoltage shutdown (OU marked as requiring controller software version 1.26 or higher in the DC 2200 table). Trigger: Voltage exceeds 120% of system nominal voltage for more than 2 seconds. |
|
| UF | Underfrequency | Shutdown | Underfrequency shutdown. Trigger: Governed frequency falls below 90% of nominal system frequency for more than 5 seconds. |
|
| UU | Undervoltage | Shutdown | Undervoltage shutdown (UU marked as requiring controller software version 1.26 or higher in the DC 2200 table). Trigger: Voltage falls below 80% of nominal system voltage for more than 10 seconds. |
|
| SCF0 | Software Communication Fault 0 | Fault (listed) | Indicates a software or communication problem within the controller (ADC 2100 per TP-6331; the DC 2200 figure in TP-6398 labels it Software Communication Fault 0). Trigger: Internal controller software/communication problem. |
|
Sources
- TP-6331 5/04, Operation — Model 12RES (ADC 2100 controller) — Kohler Co. official manual, as reproduced on ManualsOnline (§2.4 Fault Shutdowns, Figure 2-3 ADC 2100 Fault Shutdown Codes)
- TP-6398 4/07, Model 12RESM1 manual (DC 2200 controller) — Kohler Co. official manual, as reproduced on ManualsLib (§2.4 Faults, Figure 2-3 DC 2200 Fault Codes)
Honest gaps — what we have not verified
Built-in battery charger fault message (RDC2)
unverified — needs manual check The only charger message in the RDC2 tables read is 'Batt Chg Flt', which Kohler defines as an input from an EXTERNAL charger via the PIM, explicitly not the built-in charger. TP-7092's 9/23 revision snippet shows the same definition. A TP-6905-era (RDC/DC) table reproduced on a non-manufacturer site defines Batt Chg Flt differently (battery voltage above 150%/18 V for >10 sec) — that older-controller definition was NOT merged into the RDC2 entry. Whether newer RCA manuals add a built-in-charger message needs a manual check of the latest TP-7092 revision.
Kohler support-center fault articles
unverified — needs manual check Searches of kohler.com / Kohler support surfaced manuals only; no Kohler-published web fault-code hub was found in this pass. Treat Kohler documentation as manual-only until a support hub is located.
24RCA/26RCA-specific and DC2 fault tables
unverified — needs manual check TP-7092 covers the 14/20RCA class and TP-6880 the RESV class; the 24/26RCA manuals and the discontinued DC2 controller's own table were not read in this pass. TP-7093 (14 RCA service manual, 5/24) exists on ManualsLib and shows the same RDC2 message names, but its fault table was not transcribed here.
High engine temperature on RDC2
unverified — needs manual check No standalone high-temperature message appears in the RDC2 Figure 2-4/2-5 rows read; TP-7092 instead ties the 20RCA enclosure thermostat to undervoltage/underspeed-type faults (§2.6 in TP-6880 makes the same point for RESV). Do not publish a Kohler RDC2 'high temp' message without a manual citation.
Two of these deserve emphasis. First, the only charger message in the RDC2 tables is Batt Chg Flt, and Kohler defines it as an input from an external charger via the PIM — a built-in-charger fault message is unverified, so we do not publish one. Second, Kohler's two RDC2 manuals state the Lo Crank Vlt threshold differently (below 8 VDC for more than 6 seconds in TP-6880 vs below 3.5 VDC in TP-7092) — the values are model- and manual-specific and are kept separate in that message's entry above, never merged into one number.
Safety note: StandbyWise publishes lookup information only — no gas-line, transfer-switch wiring, or internal repair instructions. Shutdown faults that Kohler routes to an authorized distributor/dealer stay dealer calls. See our disclaimer.