Kohler hub

Kohler Error Codes

Plain-English meanings for Kohler standby generator fault messages, taken from Kohler's own operation manuals — never from dealer blogs. Unlike Generac, Kohler publishes no web fault-code hub: its fault documentation is manual-only, so every message below is cited to the specific Kohler manual (TP number and section) it came from. This page covers the current RDC2 controller in full, plus the older ADC 2100 / DC 2200 two-letter codes in a separate section — the two systems name the same faults differently, so we never merge them.

Looking for Generac instead? The Generac error-code hub covers Generac codes — Generac codes live there, Kohler codes live here. You can also search the verified database with the Fault Code Lookup tool.

Warnings vs shutdowns — how the RDC2 controller behaves

Warning (W)

On RDC2, a warning displays a fault message but the set does not shut down; the controller resets automatically after the warning condition is corrected (TP-7092 §2.5.1).

Shutdown (SD)

On RDC2, a shutdown stops the set automatically and displays a fault message; the OFF LED flashes; on some faults the engine cooldown cycle runs before shutdown (marked * in the tables). Shutdown switches reset when the problem is corrected, but the controller fault does not clear until the controller is reset; the set cannot be restarted until the fault is corrected and the controller is reset (TP-7092 §2.5.2, §2.5.5).

Kohler's own reset rule, stated as the manuals state it: always identify and correct the cause before resetting — the set cannot be restarted until the fault is corrected and the controller is reset. In the tables below, a shutdown marked “cooldown first” runs the engine cooldown cycle before stopping on some faults.

Sources

RDC2 fault messages — all 26 verified

Current controllers on the RCA and RESV lines. Click a message to jump to its full entry — meaning, trigger, and the checks Kohler's table itself lists.

Displayed messageTypeWhat it meansManual
AC Sens LossShutdownWarning (1 sec) / Shutdown (3 sec)AC sensing lost — in Auto mode, generator output AC sensing is lost.TP-6880 (RESV)
Accy PwrOver WarningWarningWarningAccessory Power Overload — an over-current fault (short circuit) on the accessory controller power output.TP-6880 (RESV)
Advanced DiagnosticShutdownShutdown (event history only)Shutdown during the reduced-speed portion of an exercise.TP-6880 (RESV)
Alt ProtectShutdownShutdownHigh generator current detected; the set shuts down to protect the alternator from damage caused by overheating the windings.TP-6880 (RESV)
ATS ComErrorWarningWarningATS communication error — warning is displayed if the ATS (Model RXT) interface connection is lost.TP-6880 (RESV)
ATS PhaseRotWarningWarningATS phase rotation mismatch — transfer switch phase rotation does not match; the ATS will not transfer.TP-6880 (RESV)
Aux InputShutdownShutdown (cooldown first)Auxiliary input — an optional customer-connected input is closed (digital input from optional PIM).TP-6880 (RESV)
Batt Chg FltWarningWarningBattery charger fault — input to the PIM from an external battery charger (NOT the built-in battery charger).TP-6880 (RESV)
Battery HighWarningWarningEngine starting battery voltage high.TP-6880 (RESV)
Battery LowWarningWarningEngine starting battery voltage low.TP-6880 (RESV)
Battery CrLo WarningWarningWarningCritically low engine starting battery voltage.TP-6880 (RESV)
Eng Speed HighShutdownShutdown (cooldown first)Engine overspeed — Kohler's overspeed equivalent on RDC2 (there is no message literally named 'Overspeed' in the RDC2 table).TP-6880 (RESV)
Eng Speed LowShutdownShutdown (cooldown first)Engine underspeed.TP-6880 (RESV)
Exer Not SchWarningWarningExercise not scheduled — no exercise is scheduled on the controller.TP-6880 (RESV)
Frequency HighShutdownShutdown (cooldown first)Governed frequency high (overfrequency).TP-6880 (RESV)
Frequency LowShutdownShutdown (cooldown first)Governed frequency low (underfrequency).TP-6880 (RESV)
Lo Crank VltWarningWarningLow cranking voltage.TP-6880 (RESV)
Locked RotorShutdownShutdownNo engine rotation is sensed during cranking (Kohler's locked-rotor / no-rotation start failure).TP-7092 (RCA)
MainPwrOverLShutdownShutdownMain power overload — an over-current fault on the 70 controller power output (short circuit).TP-6880 (RESV)
Not in AutoWarningWarningThe generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.TP-6880 (RESV)
Oil Press LowShutdownShutdown (cooldown first)Low oil pressure shutdown (LOP switch). Kohler notes the low oil pressure shutdown does not protect against low oil level.TP-6880 (RESV)
Over CrankShutdownShutdownOvercrank — the generator failed to start.TP-6880 (RESV)
Spd Sens FltShutdownShutdownEngine speed sensor fault — the speed sensor has failed or the engine stalled. This is Kohler's RPM/speed-signal-loss equivalent on RDC2.TP-6880 (RESV)
Total Power HighShutdownShutdownMeasured load exceeds the generator set rating.TP-6880 (RESV)
Volts L1-L2 HighShutdownShutdown (cooldown first)Generator output voltage high (overvoltage).TP-6880 (RESV)
Volts L1-L2 LowShutdownShutdown (cooldown first)Generator output voltage low (undervoltage).TP-6880 (RESV)

RDC2 messages in detail

AC Sens Loss

ShutdownVerified against a Kohler manual
What this message means
AC sensing lost — in Auto mode, generator output AC sensing is lost.
What triggers it
Detection begins 10 seconds after crank disconnect. Warning after 1 second if no output detected after crank disconnect; shutdown after 3 seconds if voltage was present and then lost.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Accy PwrOver Warning

WarningVerified against a Kohler manual
What this message means
Accessory Power Overload — an over-current fault (short circuit) on the accessory controller power output.
What triggers it
Over-current on the accessory controller power output.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Advanced Diagnostic

ShutdownVerified against a Kohler manual
What this message means
Shutdown during the reduced-speed portion of an exercise.
What triggers it
Fault during reduced-speed exercise; event history shows 'Advanced Diagnostic Active'; the engine then restarts, runs at full speed for 2 minutes, and stops; controller returns to AUTO and the exercise schedule does not change.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • If the generator set does not restart and return to AUTO, check for other faults (per source).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Alt Protect

ShutdownVerified against a Kohler manual
What this message means
High generator current detected; the set shuts down to protect the alternator from damage caused by overheating the windings.
What triggers it
High generator current (10RESV and 12RESV only).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Reduce the load.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

ATS ComError

WarningVerified against a Kohler manual
What this message means
ATS communication error — warning is displayed if the ATS (Model RXT) interface connection is lost.
What triggers it
Loss of connection to the transfer switch interface board (§2.5.3).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check communication wiring between transfer switch interface board and generator set.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

ATS PhaseRot

WarningVerified against a Kohler manual
What this message means
ATS phase rotation mismatch — transfer switch phase rotation does not match; the ATS will not transfer.
What triggers it
Phase rotation mismatch at the transfer switch.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Correct the ATS connection — dealer-level (source refers to ATS installation manual/wiring diagrams).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Aux Input

ShutdownVerified against a Kohler manual
What this message means
Auxiliary input — an optional customer-connected input is closed (digital input from optional PIM).
What triggers it
Optional PIM digital input closed.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check customer-supplied equipment.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Batt Chg Flt

WarningVerified against a Kohler manual
What this message means
Battery charger fault — input to the PIM from an external battery charger (NOT the built-in battery charger).
What triggers it
Signal from an external battery charger via the PIM.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check the external battery charger.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Source note — read carefully. This is the only charger-related message in the RDC2 table, and it concerns an external charger, not the built-in charger. No RDC2 'charger missing AC' equivalent was found in the manuals read — see gaps.

Kohler source

Battery High

WarningVerified against a Kohler manual
What this message means
Engine starting battery voltage high.
What triggers it
Battery voltage rises above 16 VDC for more than 10 seconds; inhibited during the engine crank cycle; clears when voltage returns to an acceptable level.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check the battery rating and condition.
  • Check the battery charger operation.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Battery Low

WarningVerified against a Kohler manual
What this message means
Engine starting battery voltage low.
What triggers it
Battery voltage falls below 12.5 VDC for more than 90 seconds when the engine is not running; not operative during the crank cycle; clears when voltage returns to an acceptable level.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check the battery rating and condition.
  • Check the battery charger operation.
  • Charge or replace the battery.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Battery CrLo Warning

WarningVerified against a Kohler manual
What this message means
Critically low engine starting battery voltage.
What triggers it
Battery voltage falls below 11 V for more than 10 seconds; inhibited during the crank cycle; clears when voltage returns to an acceptable level.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check the battery rating and condition.
  • Check the battery charger operation.
  • Charge or replace the battery.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Eng Speed High

ShutdownVerified against a Kohler manual
What this message means
Engine overspeed — Kohler's overspeed equivalent on RDC2 (there is no message literally named 'Overspeed' in the RDC2 table).
What triggers it
Engine speed exceeds 115% of normal running speed for more than 0.3 seconds.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Eng Speed Low

ShutdownVerified against a Kohler manual
What this message means
Engine underspeed.
What triggers it
Engine speed drops below 85% of normal running speed for more than 3 seconds.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Reduce the load.
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Exer Not Sch

WarningVerified against a Kohler manual
What this message means
Exercise not scheduled — no exercise is scheduled on the controller.
What triggers it
No exercise schedule set.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • See §3.6 of the manual for setting the exerciser (owner-level controller setting).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Frequency High

ShutdownVerified against a Kohler manual
What this message means
Governed frequency high (overfrequency).
What triggers it
Frequency exceeds 110% of the system frequency setpoint for more than 10 seconds; function becomes active 10 seconds after engine start (10-second inhibit).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Frequency Low

ShutdownVerified against a Kohler manual
What this message means
Governed frequency low (underfrequency).
What triggers it
Frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below the setting for more than 60 seconds; 10-second inhibit after start.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Reduce the load and restart the generator set.
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Lo Crank Vlt

WarningVerified against a Kohler manual
What this message means
Low cranking voltage.
What triggers it
TP-6880: battery voltage falls below 8 VDC for more than 6 seconds while the starter is engaged. TP-7092 (14/20RCA) states it differently: battery voltage dropped below 3.5 VDC during engine cranking (no duration stated).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Charge or replace the battery.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Source note — read carefully. CONFLICT KEPT SEPARATE: the two RDC2 manuals state different thresholds (8 VDC/6 sec in TP-6880 for RESV models vs 3.5 VDC in TP-7092 for RCA models). Do not publish a single threshold without naming the model/manual.

Kohler source

Locked Rotor

ShutdownVerified against a Kohler manual
What this message means
No engine rotation is sensed during cranking (Kohler's locked-rotor / no-rotation start failure).
What triggers it
Shuts down 3 seconds after the fault is detected.
Applies to
RDC2 — 14RCA/14RCAL, 20RCA/20RCAL class (TP-7092); not present in the TP-6880 RESV table read
Checks Kohler lists
  • Check the battery.
  • Check for loose connections.
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

MainPwrOverL

ShutdownVerified against a Kohler manual
What this message means
Main power overload — an over-current fault on the 70 controller power output (short circuit).
What triggers it
Over-current/short circuit on the controller's main power output.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).
  • Manual's check column also lists checking for a shorted run relay and wiring for short circuits — dealer-level, not transcribed as steps.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Not in Auto

WarningVerified against a Kohler manual
What this message means
The generator set is not in Automatic (standby) mode; remote start/stop commands from a transfer switch or remote switch will be ignored.
What triggers it
Controller not in AUTO.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Press AUTO to place the generator set in Automatic mode, when appropriate.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Oil Press Low

ShutdownVerified against a Kohler manual
What this message means
Low oil pressure shutdown (LOP switch). Kohler notes the low oil pressure shutdown does not protect against low oil level.
What triggers it
The LOP switch indicates low oil pressure for more than 5 seconds; function becomes active 30 seconds after crank disconnect (30-second inhibit).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check for leaks in the lubrication system.
  • Check the oil level and add oil if the level is low.
  • Check the oil pressure switch and wiring — dealer-level beyond the oil-level check.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Over Crank

ShutdownVerified against a Kohler manual
What this message means
Overcrank — the generator failed to start.
What triggers it
Three unsuccessful starting attempts.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Check the fuel supply, spark plug, and battery.
  • Check for loose connections.
  • Contact an authorized distributor/dealer for service if the problem continues (dealer-level beyond the listed checks).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Spd Sens Flt

ShutdownVerified against a Kohler manual
What this message means
Engine speed sensor fault — the speed sensor has failed or the engine stalled. This is Kohler's RPM/speed-signal-loss equivalent on RDC2.
What triggers it
Speed sensor failure or engine stall.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Total Power High

ShutdownVerified against a Kohler manual
What this message means
Measured load exceeds the generator set rating.
What triggers it
Load greater than 102% of the generator set power rating for more than 1 minute (10RESV and 12RESV only).
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Reduce the load.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Volts L1-L2 High

ShutdownVerified against a Kohler manual
What this message means
Generator output voltage high (overvoltage).
What triggers it
Output voltage exceeds 120% of system nominal voltage for more than 2 seconds.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Volts L1-L2 Low

ShutdownVerified against a Kohler manual
What this message means
Generator output voltage low (undervoltage).
What triggers it
Output voltage falls below 80% of nominal system voltage for more than 10 seconds.
Applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
Checks Kohler lists
  • Reduce the load and restart the generator set.
  • Model 20RCA/20RCAL only (TP-7092): check the enclosure thermostat and reset if tripped — see manual §5.6.
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Kohler source

Legacy codes — ADC 2100 / DC 2200 (12RES era)

Separate system, separate names. Older Kohler controllers (ADC 2100 and DC 2200, 12RES era) show short two-letter codes instead of RDC2 message text — overspeed is literally “OS” here, where RDC2 says “Eng Speed High.” This section is kept separate on purpose; do not read an RDC2 meaning into a legacy code or the other way around.

CodeMessageTypeMeaning & trigger (per Kohler)Checks Kohler lists
AFAuxiliary FaultShutdown (input shutdown)Auxiliary fault, input shutdown — listed as 'Not used' on the 12RES. Trigger: Auxiliary input shutdown (not used on this model).
  • — (not used)
HEHigh Engine TemperatureShutdownHigh engine temperature shutdown. Trigger: Engine coolant temperature exceeds the maximum temperature for more than 5 seconds; protective becomes active after the engine reaches crank disconnect speed.
  • Check for blocked air inlets and exhaust outlets.
LBLow Battery VoltageWarning (does not shut down)Low engine starting battery voltage warning. Trigger: DC 2200 table (TP-6398): battery voltage falls below 8 VDC (12 VDC system) or 16 VDC (24 VDC system) for more than 10 seconds when the engine is not running.
  • Check the battery rating and condition.
  • Check the battery charger operation.
  • Charge or replace the battery.
LCL / LOCLow Coolant Level / Loss of CoolantShutdown (listed)Low coolant level / loss of coolant — both listed as not used on air-cooled models. Trigger: Not used on air-cooled 12RES.
  • — (not used)
LOPLow Oil PressureShutdownLow oil pressure shutdown. The manual notes this shutdown does not protect against low oil level. Trigger: Low oil pressure condition exists for more than 5 seconds; protective becomes active 30 seconds after the engine has reached crank disconnect speed (30-second inhibit).
  • Check for leaks in the lubrication system.
  • Check the oil level and add oil if the level is low.
OCOvercrankShutdownOvercrank shutdown — the generator failed to start. Trigger: After 3 unsuccessful starting attempts; the crank cycle is three attempts of 15 seconds cranking and 15 seconds rest. The set also shuts down if no engine rotation is sensed during cranking (1 second after detection).
  • Check the fuel supply, spark plug, and battery.
  • Check for loose connections.
  • Contact an authorized distributor/dealer for service if the problem continues (dealer-level).
OFOverfrequencyShutdownOverfrequency shutdown. Trigger: Governed frequency exceeds 110% of the system's frequency setpoint for more than 5 seconds.
  • Contact an authorized distributor/dealer for service (dealer-level).
OSOverspeedShutdownOverspeed shutdown (on these older controllers the message is literally 'Overspeed', unlike RDC2's 'Eng Speed High'). Trigger: Engine speed exceeds 115% of normal running speed for more than 0.3 seconds.
  • Contact an authorized distributor/dealer for service (dealer-level).
OUOvervoltageShutdownOvervoltage shutdown (OU marked as requiring controller software version 1.26 or higher in the DC 2200 table). Trigger: Voltage exceeds 120% of system nominal voltage for more than 2 seconds.
  • Contact an authorized distributor/dealer for service (dealer-level).
UFUnderfrequencyShutdownUnderfrequency shutdown. Trigger: Governed frequency falls below 90% of nominal system frequency for more than 5 seconds.
  • Contact an authorized distributor/dealer for service (dealer-level).
UUUndervoltageShutdownUndervoltage shutdown (UU marked as requiring controller software version 1.26 or higher in the DC 2200 table). Trigger: Voltage falls below 80% of nominal system voltage for more than 10 seconds.
  • Reduce the load / contact an authorized distributor/dealer for service (dealer-level).
SCF0Software Communication Fault 0Fault (listed)Indicates a software or communication problem within the controller (ADC 2100 per TP-6331; the DC 2200 figure in TP-6398 labels it Software Communication Fault 0). Trigger: Internal controller software/communication problem.
  • Contact an authorized distributor/dealer for service (dealer-level).

Sources

Honest gaps — what we have not verified

Built-in battery charger fault message (RDC2)

unverified — needs manual check The only charger message in the RDC2 tables read is 'Batt Chg Flt', which Kohler defines as an input from an EXTERNAL charger via the PIM, explicitly not the built-in charger. TP-7092's 9/23 revision snippet shows the same definition. A TP-6905-era (RDC/DC) table reproduced on a non-manufacturer site defines Batt Chg Flt differently (battery voltage above 150%/18 V for >10 sec) — that older-controller definition was NOT merged into the RDC2 entry. Whether newer RCA manuals add a built-in-charger message needs a manual check of the latest TP-7092 revision.

Kohler support-center fault articles

unverified — needs manual check Searches of kohler.com / Kohler support surfaced manuals only; no Kohler-published web fault-code hub was found in this pass. Treat Kohler documentation as manual-only until a support hub is located.

24RCA/26RCA-specific and DC2 fault tables

unverified — needs manual check TP-7092 covers the 14/20RCA class and TP-6880 the RESV class; the 24/26RCA manuals and the discontinued DC2 controller's own table were not read in this pass. TP-7093 (14 RCA service manual, 5/24) exists on ManualsLib and shows the same RDC2 message names, but its fault table was not transcribed here.

High engine temperature on RDC2

unverified — needs manual check No standalone high-temperature message appears in the RDC2 Figure 2-4/2-5 rows read; TP-7092 instead ties the 20RCA enclosure thermostat to undervoltage/underspeed-type faults (§2.6 in TP-6880 makes the same point for RESV). Do not publish a Kohler RDC2 'high temp' message without a manual citation.

Two of these deserve emphasis. First, the only charger message in the RDC2 tables is Batt Chg Flt, and Kohler defines it as an input from an external charger via the PIM — a built-in-charger fault message is unverified, so we do not publish one. Second, Kohler's two RDC2 manuals state the Lo Crank Vlt threshold differently (below 8 VDC for more than 6 seconds in TP-6880 vs below 3.5 VDC in TP-7092) — the values are model- and manual-specific and are kept separate in that message's entry above, never merged into one number.

Safety note: StandbyWise publishes lookup information only — no gas-line, transfer-switch wiring, or internal repair instructions. Shutdown faults that Kohler routes to an authorized distributor/dealer stay dealer calls. See our disclaimer.