Kohler RDC2 fault message — liquid-cooled (TP-6905)
Battery Low
What Kohler's TP-6905 operation manual says about the “Battery Low” message — its meaning, its documented trigger, and the checks Kohler itself lists — is below. Anything beyond those checks is dealer work.
- What this message means
- Low Battery Voltage. Engine starting battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds when the engine is not running. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.
- What triggers it
- Battery voltage below the battery voltage setting (typically 12.5 V) for more than 90 seconds, engine not running.
- Which generators it applies to
24RCL, 30RCL, 38RCLB (RDC2, liquid-cooled)
- Controller: RDC2 (TP-6905, liquid-cooled RCL)
- Checks Kohler lists
- Check the battery rating and condition.
- Check the battery charger operation.
- Charge or replace the battery.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
What it costs
- $0 — if charging restores the battery
- This warning triggers when battery voltage falls below the battery voltage setting (typically 12.5 volts) for more than 90 seconds, with the engine not running (inhibited during cranking), and it clears when the battery voltage returns to an acceptable level. Kohler's listed actions include: charge or replace the battery (TP-6905). If charging restores the battery and the warning clears, the cost is $0.
- The part
Starting battery — Group 51, 500 CCA class
- Fitment label: no battery group or CCA specification for this model family appears in Kohler's manuals. The prices below are for the Group 51 / 500 CCA class verified for Kohler's RCA line, published here as a class figure for this family — not a verified fitment.
- Interstate Batteries lists its MT-51 flooded battery (Group 51, 500 CCA) at an SRP of $209.95.
- Advance Auto Parts lists the DieHard Silver battery, Group 51 (part 51-2), 500 CCA, at $214.99.
- Kohler names no battery brand or part number — the battery is purchased separately, and the specification is the group size and the CCA rating.
- Group 51 only: Group 51R batteries reverse the terminal orientation and do not meet this specification, so no 51R price is used here.
- At a dealer
If a technician replaces the battery instead: VoltShield's Kohler cost breakdown puts a battery replacement on a 26 kW air-cooled Kohler at $320–$450 (secondary sourcing, from Q4 2024 vendor invoices).
Published Kohler service figures — none is specific to this message, because no dealer publishes a price for a single fault message: a $595 single service visit for liquid-cooled units, plus tax (HomeSafe Generators & Electrical); a $249 service call including travel and up to 60 minutes of on-site diagnosis (GSHA Services). Published plan figures — $249–$499 per year (Four Seasons) and $300 per year for two visits a year (Watts Up Electric) — are published for air-cooled residential service.
Parts price only — labor varies by dealer.
Every price on this page was checked in November 2026 against the source named next to it. Prices change; the part numbers do not.
Seeing a different message — or a Generac code?
Browse the full Kohler error-code hub for every verified RDC2 message and the legacy ADC/DC codes, use the Fault Code Lookup tool, or see the separate Generac error-code hub — the two brands' codes are never merged.
Kohler source
- TP-6905 4/16b — Operation, Residential/Light Commercial Generator Sets, Models 24RCL, 30RCL, 38RCLB; Controller: RDC2 — Kohler Co. (ManualsLib reproduction of the Kohler manual) (Figure 2-5 Controller Fault Messages, Section 2, pp. 25–28)