Kohler RDC2 fault message — liquid-cooled (TP-6905)

Battery High

Liquid-cooled RDC2 (TP-6905). This message is from Kohler's liquid-cooled RCL table (24RCL, 30RCL, 38RCLB) in manual TP-6905. It is kept separate from the air-cooled RDC2 tables on purpose: the liquid-cooled table adds ECM, coolant, and ignition messages with no air-cooled equivalent, and where the same fault name appears in both, the manuals may state it differently. Do not apply this entry to an air-cooled RCA or RESV unit.

What Kohler's TP-6905 operation manual says about the “Battery High” message — its meaning, its documented trigger, and the checks Kohler itself lists — is below. Anything beyond those checks is dealer work.

Verified against a Kohler manualWarningWarning
What this message means
High Battery Voltage. Engine starting battery voltage rises above 133% (16 V) of the battery voltage setting for more than 10 seconds. Inhibited during the engine crank cycle. Clears when the battery voltage returns to an acceptable level.
What triggers it
Battery voltage above 133% (16 V) of the battery voltage setting for more than 10 seconds.
Which generators it applies to

24RCL, 30RCL, 38RCLB (RDC2, liquid-cooled)

  • Controller: RDC2 (TP-6905, liquid-cooled RCL)
Checks Kohler lists
  • Check the battery rating and condition.
  • Check the battery charger operation.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

What it costs

$0 — if the voltage returns to the acceptable range
This warning triggers when battery voltage rises above 133% (16 V) of the battery voltage setting for more than 10 seconds (inhibited during cranking), and it clears when the battery voltage returns to an acceptable level. Kohler's listed checks are the battery rating and condition, and the battery charger operation. If the voltage returns to the acceptable range and the warning clears, the cost is $0.
The part

If the battery itself is the cause, the replacement prices as the battery class below. If the charging side is the cause, there is no part to price: the built-in charger is part of the RDC2 controller.

Starting battery — Group 51, 500 CCA class

  • Fitment label: no battery group or CCA specification for this model family appears in Kohler's manuals. The prices below are for the Group 51 / 500 CCA class verified for Kohler's RCA line, published here as a class figure for this family — not a verified fitment.
  • Interstate Batteries lists its MT-51 flooded battery (Group 51, 500 CCA) at an SRP of $209.95.
  • Advance Auto Parts lists the DieHard Silver battery, Group 51 (part 51-2), 500 CCA, at $214.99.
  • Kohler names no battery brand or part number — the battery is purchased separately, and the specification is the group size and the CCA rating.
  • Group 51 only: Group 51R batteries reverse the terminal orientation and do not meet this specification, so no 51R price is used here.
At a dealer

Published Kohler service figures — none is specific to this message, because no dealer publishes a price for a single fault message: a $595 single service visit for liquid-cooled units, plus tax (HomeSafe Generators & Electrical); a $249 service call including travel and up to 60 minutes of on-site diagnosis (GSHA Services). Published plan figures — $249–$499 per year (Four Seasons) and $300 per year for two visits a year (Watts Up Electric) — are published for air-cooled residential service.

Parts price only — labor varies by dealer.

Every price on this page was checked in November 2026 against the source named next to it. Prices change; the part numbers do not.

How warnings clear. On the RDC2, a warning displays a fault message but the set does not shut down; the controller resets automatically after the warning condition is corrected. If the warning keeps coming back, contact an authorized Kohler distributor/dealer.

Seeing a different message — or a Generac code?

Browse the full Kohler error-code hub for every verified RDC2 message and the legacy ADC/DC codes, use the Fault Code Lookup tool, or see the separate Generac error-code hub — the two brands' codes are never merged.