Kohler RDC2 fault message

Volts L1-L2 Low

What Kohler's own operation manual says about the “Volts L1-L2 Low” message — its meaning, its documented trigger, and the checks Kohler itself lists — is below. Anything beyond those checks is dealer work.

Verified against a Kohler manualShutdownShutdown (cooldown first)
What this message means
Generator output voltage low (undervoltage).
What triggers it
Output voltage falls below 80% of nominal system voltage for more than 10 seconds.
Which generators it applies to

RDC2 — 8/10/12RESV(L) (TP-6880)

  • Controller: Kohler RDC2
Checks Kohler lists
  • Reduce the load and restart the generator set.
  • Model 20RCA/20RCAL only (TP-7092): check the enclosure thermostat and reset if tripped — see manual §5.6.
  • Contact an authorized distributor/dealer for service (dealer-level).

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Before you reset anything. Kohler's own reset rule: always identify and correct the cause before resetting — the set cannot be restarted until the fault is corrected and the controller is reset. If the message returns after the checks Kohler lists above, contact an authorized Kohler distributor/dealer rather than repeatedly clearing and restarting the unit.