Kohler RDC2 fault message
Oil Press Low
What Kohler's own operation manual says about the “Oil Press Low” message — its meaning, its documented trigger, and the checks Kohler itself lists — is below. Anything beyond those checks is dealer work.
Verified against a Kohler manualShutdownShutdown (cooldown first)
- What this message means
- Low oil pressure shutdown (LOP switch). Kohler notes the low oil pressure shutdown does not protect against low oil level.
- What triggers it
- The LOP switch indicates low oil pressure for more than 5 seconds; function becomes active 30 seconds after crank disconnect (30-second inhibit).
- Which generators it applies to
RDC2 — 8/10/12RESV(L) (TP-6880)
- Controller: Kohler RDC2
- Checks Kohler lists
- Check for leaks in the lubrication system.
- Check the oil level and add oil if the level is low.
- Check the oil pressure switch and wiring — dealer-level beyond the oil-level check.
These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.
Before you reset anything. Kohler's own reset rule: always identify and correct the cause before resetting — the set cannot be restarted until the fault is corrected and the controller is reset. If the message returns after the checks Kohler lists above, contact an authorized Kohler distributor/dealer rather than repeatedly clearing and restarting the unit.
Seeing a different message — or a Generac code?
Browse the full Kohler error-code hub for every verified RDC2 message and the legacy ADC/DC codes, use the Fault Code Lookup tool, or see the separate Generac error-code hub — the two brands' codes are never merged.
Kohler source
- TP-6880 2/21e, Operation — Residential/Commercial Generator Sets, Models 10/12RESV, 10/12RESVL (similar: 8RESV/L), Controller: RDC2 — Kohler Co. (resources.kohler.com — official Kohler PDF) (Figure 2-4 Controller Fault Messages (pp. 27–28) and §2.5 Faults)