Kohler RDC2 fault message

Lo Crank Vlt

What Kohler's own operation manual says about the “Lo Crank Vlt” message — its meaning, its documented trigger, and the checks Kohler itself lists — is below. Anything beyond those checks is dealer work.

Verified against a Kohler manualWarningWarning
What this message means
Low cranking voltage.
What triggers it
TP-6880: battery voltage falls below 8 VDC for more than 6 seconds while the starter is engaged. TP-7092 (14/20RCA) states it differently: battery voltage dropped below 3.5 VDC during engine cranking (no duration stated).
Which generators it applies to

RDC2 — 8/10/12RESV(L) (TP-6880)

  • Controller: Kohler RDC2
Checks Kohler lists
  • Charge or replace the battery.

These are only the checks Kohler itself lists. Anything beyond them — internal wiring, sensors, switches, or alternator work — is dealer work, and we do not publish instructions for it.

Source note — read carefully. CONFLICT KEPT SEPARATE: the two RDC2 manuals state different thresholds (8 VDC/6 sec in TP-6880 for RESV models vs 3.5 VDC in TP-7092 for RCA models). Do not publish a single threshold without naming the model/manual.
How warnings clear. On the RDC2, a warning displays a fault message but the set does not shut down; the controller resets automatically after the warning condition is corrected. If the warning keeps coming back, contact an authorized Kohler distributor/dealer.