Fuel consumption for the Guardian Series 26 kW (model 7290 / 7291 (G007290-0 / G007291-0)), transcribed from Generac's own spec sheet — nothing interpolated, nothing carried over from another size or series. This model is rated 26 kW on propane and 22.5 kW on natural gas, with a 999cc G-Force 1000, 2 cylinder engine.
Consumption (Generac spec)
| Fuel | 50% load | 100% load |
|---|---|---|
| Natural gas | 188 ft³/hr | 333 ft³/hr |
| Propane (LP) | 2.06 gal/hr (75 ft³/hr) | 3.63 gal/hr (132 ft³/hr) |
Generac spec-sheet source
- SPEC 26KW GUARDIAN HSB EN — Guardian 26 kW Specification Sheet (G007290-0 / G007291-0) — Generac Power Systems (official spec sheet; values read from the spec-sheet table) (26 kW Specifications — Generator / Engine tables. Note: spec sheet is the Downloads listing on the Generac 26kW product page.)
Worked running-cost example
Costs depend on your local fuel price, which we do not guess. The figures below use example prices only — natural gas at $1.50 per therm (1 therm = 100 ft³) and propane at $3.00 per gallon, the same starting defaults as our fuel cost calculator. Substitute your own bill's price for the real number.
| Fuel (example price) | Cost/hr at 50% load | Cost/hr at 100% load |
|---|---|---|
| Natural gas ($1.50/therm) | $2.82/hr | $5.00/hr |
| Propane ($3.00/gal) | $6.18/hr | $10.89/hr |
- A 24-hour outage at 50% load on natural gas: 188 × 24 = 4,512 ft³ = 45.12 therms ≈ $67.68 at the example price.
- The same 24 hours at 50% load on propane: 2.06 × 24 = 49.44 gallons ≈ $148.32 at the example price.
Real outages sit between the two load columns, so treat 50% and 100% as the floor and ceiling of the range. For your own outage length and fuel price, run the Fuel & Running Cost Calculator — it uses these same verified figures.
Comparing series? The Next Generation Series 26 kW burns different amounts
Generac publishes different consumption for the same kW size in each series (natural gas: 182/316 ft³/hr at 50%/100% load). See the Next Generation 26 kW fuel page.