Generac Maintenance Schedule
This is Generac's own published schedule, transcribed in full — not a dealer's summary of it. Generac Next Generation Series 10-28 kW air-cooled and Generac Guardian Series 10-26 kW air-cooled (2017 to present), per Generac support. Generac states the table is an example/for reference — the model's owner's manual maintenance section governs. Generac presents the table as an example for reference; your model's owner's manual governs if anything differs.
Not sure what is due on your unit right now?
Enter your run hours and last-service timing into the Maintenance Due Calculator — it works directly from this schedule. For the parts each service needs, see the Battery & Maintenance Kit Finder and the kit 6485 page.
The schedule, as Generac publishes it
| Task | Daily if running continuously or before each use | Every Year | Schedule A — every two years or 200 hours | Schedule B — every four years or 400 hours |
|---|---|---|---|---|
| Inspect enclosure louvers for dirt and debris * | ● | — | — | — |
| Inspect lines and connections for fuel or oil leaks | ● | — | — | — |
| Check engine oil level | ● | — | — | — |
| Inspect for water intrusion ** | — | ● | — | — |
| Perform fuel system leak test | — | ● | — | — |
| Check battery condition, electrolyte level, and state of charge | — | — | ● | — |
| Replace engine oil and oil filter † | — | — | ● | ● |
| Replace engine air filter | — | — | — | ● |
| Clean; inspect spark plug gap; replace if necessary | — | — | — | ● |
| Inspect/adjust valve clearance (where applicable) ‡ | — | — | — | ● |
| Inspect/clean sediment trap | — | See local codes and guidelines | — | — |
The periods, in plain terms
Break-in / Schedule C
After the first 25 hours of run time (PowerPact 7.5 kW: first 20 hours)
Change engine oil and oil filter after the break-in period. Units ship with conventional oil; do not switch to synthetic before break-in is reached. 'Schedule C' designation is used for Next Generation series.
Yearly maintenance
Every 100 hours or every year, whichever comes first
Includes water-intrusion inspection and fuel system leak test (see yearly column).
Schedule A
Every 200 hours or every two years, whichever comes first
Oil and oil filter replacement; battery condition/electrolyte/charge check.
Schedule B
Every 400 hours or every four years, whichever comes first
Schedule A items plus air filter replacement, spark plug clean/gap-inspect/replace, valve clearance where applicable.
Continuous use
Daily (every 24 hours of continuous running)
Daily-column checks apply when running continuously or before each use.
Important notes from Generac
- Extreme environments: generators operating below 40°F (<4.4°C) or above 85°F (>29.4°C) require an oil and oil filter change every year or after every 100 hours of run time since last service.
- ‡ Inspect/adjust valve clearance after the first 25 hours of run time (where applicable).
- Next Generation series generators and the 14 & 18 kW Guardian series generators use hydraulic lifters and therefore do NOT require a valve clearance inspection or adjustment.
- * / ** footnote markers appear in Generac's table as printed; their footnote text was not reproduced in the support article text read in this pass.
We name tasks exactly as Generac names them. We do not publish step-by-step service procedures — your owner's manual and your dealer are the sources for how each task is performed, and anything involving fuel-system or electrical work belongs to a licensed professional.
Sources
- Where Can I Find the Maintenance Schedule for My Generac Home Standby Generator? — Generac (support.generac.com) (Maintenance Schedule Table Example; Important notes; Maintenance Periods)
- How do I perform the yearly or annual maintenance for my home standby generator? — Generac (support.generac.com) (When do I need to change my oil?; What type of oil do I need?)